Leave Your Message
China EPS Fire Emergency Power Supply - Reliable Suppliers & Factory for Fire Protection Solutions

Hot Products

Products Categories
Featured Products

China EPS Fire Emergency Power Supply - Reliable Suppliers & Factory for Fire Protection Solutions

The EPS (Emergency Power Supply) fire emergency power supply is a vital centralized power source specifically engineered for fire protection in China. This reliable system is engineered to swiftly deliver stable electrical support to fire protection facilities, including emergency lighting, fire pumps, fire elevators, and fire alarm systems, during power outages or interruptions. As a leading factory and supplier in the industry, we ensure that our EPS units provide uninterrupted power, safeguarding lives and property in critical situations. Trust our quality solutions for your fire safety needs

    EPS fire emergency power supplies can be categorized into the following three types based on their application:

    💡
    Emergency Lighting Type

    Primarily used to provide centralized power supply for emergency lighting fixtures during building fires or emergencies.

    Hybrid Type

    Capable of supporting both emergency lighting and mixed loads such as fire pumps and fire elevators.

    🔄
    Power Inverter Type

    Specifically designed for power loads like electric motors, providing a variable-frequency three-phase emergency power system that supports soft motor starts to reduce startup impact.

    🔧 Technical Features
    🛡️ High Reliability

    Incorporates redundant design with forced start, overload operation, and segmented battery management to ensure continuous power supply during emergencies.

    ⏱️ Rapid Switchover

    Switching time between utility power and emergency power typically under 5 seconds (millisecond-level for select models), meeting fire protection systems' demand for instantaneous power supply.

    📊 Intelligent Management

    Equipped with smart monitoring and alarm functions to track real-time power status and battery health, facilitating timely maintenance and management.

    🌐 High Adaptability

    Capable of handling capacitive, inductive, and mixed loads with robust overload capacity and surge resistance, suitable for diverse complex environments.

    🏢 Application Scenarios

    EPS fire emergency power supplies are widely deployed in the following scenarios:

    🔥 Building Fire Protection

    Provides power support for emergency lighting, fire pumps, fire elevators, fire alarm systems, and other fire protection equipment.

    🏥 Medical Facilities

    Ensures emergency power supply for critical areas like operating rooms and intensive care units, maintaining uninterrupted medical operations.

    🛣️ Public Infrastructure

    Provides backup power for road lighting, tunnel illumination, electrical facilities, industrial plants, and mining operations.

    🏭 Industrial Production

    Delivers standby power to high-demand equipment in chemical, metallurgical, and electronics industries, preventing production halts and equipment damage during outages.

    📋 Technical Specifications
    Rated Capacity 16kwh ~ 800kwh
    AC Input Phase 3 Phase 4 Wire + PE
    Voltage 380V ± 15%
    Frequency 50Hz ± 5%
    Emergency Output Voltage 380V ± 3%
    Frequency 50/60Hz ± 0.5Hz
    Wave Form Pure Sine Wave
    THD <5% (0–100% Under Linear Load)
    Inverter Efficiency >92%
    Overload Capacity 120% — 35s
    Battery Type LiFePO4
    Voltage 153 ~ 614VDC
    Standby Time 1 ~ 24H (Design requirements may specify configuration)
    Charging Time 1 ~ 24H (Design requirements may specify configuration)
    Conversion Time <0.5s
    Protection Emergency state overload protection, output open-circuit/short-circuit protection; battery under-voltage protection
    Alert Battery under-voltage, battery connection failure, charger malfunction, sustained overload, inverter failure, etc.
    Ambient Temperature -20 ~ 55°C
    Humidity <90% RH, non-condensing
    Altitude <2000m
    Noise No noise during mains power output; Emergency output mode <55dB
    Communications RS485 / CAN (Optional)
    Frequently Asked Questions
    Q What are the main types of EPS fire emergency power supplies?
    EPS fire emergency power supplies are available in three main types: Emergency Lighting Type (for centralized emergency lighting), Hybrid Type (supporting both lighting and mixed loads such as fire pumps and elevators), and Power Inverter Type (designed for motor-driven equipment with soft-start capability).
    Q How fast is the switchover from mains power to emergency power?
    The standard conversion time is less than 0.5 seconds. Certain high-performance models offer millisecond-level switching, ensuring fire protection systems receive instantaneous and uninterrupted power during an outage.
    Q What type of battery does the EPS system use, and how long can it last?
    The system uses LiFePO4 (Lithium Iron Phosphate) batteries operating at 153–614VDC. Both standby time and charging time can be configured between 1 and 24 hours based on specific design requirements.
    Q What protection and alert functions are built into the EPS system?
    The system includes overload protection during emergency state, output open-circuit and short-circuit protection, and battery under-voltage protection. Alerts are triggered for conditions such as battery under-voltage, battery connection failure, charger malfunction, sustained overload, and inverter failure.
    Q In which industries and environments can EPS fire emergency power supplies be used?
    EPS systems are suitable for a wide range of applications including building fire protection, hospitals and medical facilities, public infrastructure (roads, tunnels, mines), and industrial sectors such as chemical, metallurgical, and electronics manufacturing. They operate in temperatures from -20°C to 55°C and at altitudes up to 2000m.
    Q What is the rated capacity range and output quality of the EPS system?
    The EPS system supports rated capacities from 16kWh to 800kWh. Emergency output delivers a pure sine wave at 380V ± 3%, with a Total Harmonic Distortion (THD) of less than 5% under linear load and an inverter efficiency exceeding 92%, ensuring stable and clean power for sensitive equipment.

    Leave Your Message